Skip to content
SAMFire Detection Solutions
All articles

Fire detection

Fire Detection in Laundry or Dry Cleaning: Which Solutions?

  • 4 min read
  • Written and published automatically
A cozy urban laundromat at night with a welcoming interior and modern washing machines.
Photo Jimmy Liao · Pexels

Blog

In brief

An industrial laundry or dry cleaning facility combines three constraints for fire detection: textile lint that clogs sensors, heat from dryers and irons that can trigger false thermal alarms, and humidity from steam machines that disrupts optical detectors. The solution involves choosing technology adapted to each zone, validated according to NBN S 21-100-1 standard, and enhanced maintenance compliant with NBN S 21-100-2.

What are the specific fire risks in an industrial laundry or dry cleaning facility?

An industrial laundry or dry cleaning facility combines several fire risk factors rarely found together elsewhere: high textile fire load, machines producing continuous heat (dryers, calenders, ironing presses), and an atmosphere laden with fibrous dust and water vapour. These three elements affect both the probability of fire outbreak and the reliability of installed detectors.

Tumble dryers are the most sensitive point: lint accumulation in exhaust ducts, combined with residual heat from heating elements, is a known cause of smouldering fires that start in ducts before spreading. The special risk area constituted by the dryer zone deserves, within the meaning of NBN S 21-100-1, specific analysis before choosing the detection type.

Why do lint and textile dust complicate fire detection?

Textile lint gradually deposits on optical sensors and in detection chambers, distorting their sensitivity in both directions: they can cause nuisance alarms by partially obstructing the optical chamber, or conversely mask a real fire start by isolating the sensor from actual smoke.

This fibrous dust also clogs filters in aspirating smoke detectors (ASD, Aspirating Smoke Detection) if they are not sized for this environment. In areas with high lint production, such as around dryers, carders or folding tables, the choice generally favours detectors designed for dusty environments, with closer maintenance rather than standard optical detectors mounted on open ceilings. NBN S 21-100-1 standard specifically requires adapting the detector type to the room's ambient conditions, not just to its surface area.

How does heat from drying and ironing machines disrupt detection?

Heat released by dryers, calenders and ironing presses creates ambient conditions close to those of an incipient fire, complicating the adjustment of heat detectors and making standard optical detection unreliable in direct proximity to machines.

A fixed-temperature heat detector placed too close to a dryer may trigger during normal operation, while a detector set too high to avoid this nuisance loses its ability to detect a real smouldering fire in the same zone. The technical response consists of favouring rate-of-rise heat detectors rather than fixed-threshold ones, which react to rapid temperature increase rather than absolute value, and positioning sensors taking into account hot air flows generated by machines rather than following uniform ceiling grid spacing.

What impact does ambient humidity have on detector choice?

Humidity and water vapour produced by washing machines, steam ironing and finishing tunnels strongly disrupt optical smoke detectors, which may interpret steam as smoke and generate recurring false alarms.

In steam ironing areas or near steam calenders, optical detection alone is generally not the most robust choice. More reliable solutions combine either multi-criteria detectors (optical and thermal combined, or even optical and CO), which cross-reference several signatures before triggering an alarm, or repositioning sensors outside direct steam plume zones. The choice must always remain consistent with the building's risk analysis and with NBN S 21-100-1 requirements on matching detector type to room operating conditions.

Which detection technologies limit false alarms while remaining reliable?

No single technology adequately covers an entire laundry: the correct principle consists of assigning different technology according to zone (textile storage, dryers, steam ironing, administrative areas), rather than standardising the installation.

ZoneDominant constraintAdapted technology
Textile storage, sorting areasLint, dustAspirating detection (ASD) with enhanced filtration, or protected optical
Dryer surroundingsHeat, risk of smouldering fire in ductsRate-of-rise heat detector, duct detection in extraction system
Ironing and steam calendersHumidity, steamMulti-criteria optical/thermal detector, installation outside steam plume
Offices, changing rooms, circulationNormal ambient conditionsStandard optical smoke detector

Duct detection, placed in dryer extraction ducts, particularly enables detection of smouldering lint fires before they spread to the room, a point often overlooked in standard installations.

How to adapt installation maintenance to this type of environment?

Maintenance of a detection installation in a laundry must be more frequent than the basic periodicity provided by NBN S 21-100-2, due to accelerated sensor fouling by lint and possible corrosion linked to permanent humidity.

Regular cleaning of optical chambers and aspiration filters, along with visual inspection of extraction ducts, limits both false alarms and actual loss of sensor sensitivity. Installed detectors must bear BOSEC certification, guaranteeing compliance with performance standards applicable in Belgium, and the maintenance plan must be documented in the building's operating file, available for inspection during checks carried out by the competent emergency zone (hulpverleningszone).

FAQ

Is a specific detector required above each industrial dryer?

There is no single quantified rule, but the dryer zone is generally treated as a special risk area: a rate-of-rise heat detector, combined with duct detection in the extraction system, is the most suitable configuration for detecting smouldering lint fires before propagation.

Why do standard optical detectors often trigger false alarms in dry cleaning facilities?

Water vapour produced by ironing and calenders has an optical signature close to that of smoke, which can fool a standard optical detector. A multi-criteria detector or positioning outside the steam plume reduces this risk.

Should lint extraction ducts be equipped with detection?

This is a recommended technical practice for this type of activity, as smouldering lint fires frequently start in ducts before reaching the room. The building's risk analysis must precisely determine installation points.

How frequently should detectors be cleaned in an industrial laundry?

The basic periodicity set by NBN S 21-100-2 must be enhanced in this type of environment, due to rapid fouling by lint and constant humidity. The BOSEC-certified installer defines the appropriate frequency based on actual exposure of each zone.

Frequently asked questions

  • fire detection
  • industrial laundry
  • dry cleaning
  • false alarms
  • nbn s 21-100
  • fire detection maintenance

Have your system checked before someone else does it for you.

On-site audit within 48 h, no obligation. You leave with a written report, whether we work together or not.

24/7 technical standby · 0800 14 145