Fire Detection in Open Space and Coworking: What Obligations in Belgium?

  • 4 min read
  • Written and published automatically
Wide-angle view of a modern minimalist white office space with clean lines and ample lighting.
Photo Andrea De Santis · Pexels

Blog

In brief

An open-plan office or coworking space remains subject to the Royal Decree of 7 July 1994 and NBN S21-100-1 for design, and NBN S21-100-2 for maintenance. The absence of partitions reduces compartmentation and accelerates smoke propagation, which often requires more optical detectors or an aspiration mesh, calculated according to ceiling height and actual obstacles on the floor plate.

What detection rules apply to open-plan offices in Belgium?

Fire detection in an open-plan office or coworking space falls under the same texts as any Belgian professional building: the Royal Decree of 7 July 1994 establishing basic standards for fire and explosion prevention, which classifies the building as low, medium or high according to its height, the NBN S21-100-1 standard for the design and installation of the detection system, and the Code on Well-being at Work (Book III, Title 3) for fire prevention in workplaces. There is no derogatory regime for open space: it is the configuration of the floor plate that imposes different technical choices, not a regulatory exception.

The difficulty comes from the geometry of the place: an open floor plate of several hundred square metres without partitions behaves differently from a corridor with closed offices, and this conditions compartmentation, smoke propagation and the number of detectors.

Why is compartmentation reduced in an open space?

Compartmentation refers to the division of a building into volumes separated by fire-resistant walls, intended to limit the spread of a fire from one room to another. In an open-plan office, the removal of internal partitions mechanically increases the surface area of the same compartment, since the walls that could have created subdivisions have disappeared in favour of a continuous floor plate.

The Royal Decree of 7 July 1994 imposes compartmentation limits that depend on the building category (low, medium, high). An open space that occupies an entire floor reaches these limits faster than a conventional plan with closed offices, which may require either partial subdivision by fire-resistant walls or curtains, or reinforcement of the detection system to compensate for the absence of these physical barriers. This choice is made on a case-by-case basis with the design office or installer.

How does smoke propagate faster in an open floor plate?

In an open space, smoke from a fire spreads across the entire surface of the floor plate without encountering a partition that would contain it locally, which reduces the time available before smoke reaches areas far from the source. The absence of internal compartmentation means that occupants located at the other end of the floor plate may be exposed to smoke before they even visually perceive the fire outbreak.

This phenomenon is consistent with Belgian statistics: 70% of fire victims are killed by smoke, at night, and half of the deaths recorded in 2025 occurred during night fires. In a building occupied continuously or in staggered hours (24/7 coworking, open space with night teams), this speed of propagation justifies more reactive and better distributed detection across the entire floor plate, rather than a simple detector per room as in a partitioned configuration.

What type of detector should be chosen for an open space or coworking space?

The choice of detector type depends on ceiling height, floor plate volume and the nature of activities (pure offices, printer areas, shared kitchen, server room). The NBN S21-100-1 standard frames this choice and requires BOSEC-certified devices.

Detector typeTypical use in open spacePoints of attention
Optical (photoelectric)Standard office areas, open meeting roomsReference for visible smoke, sensitive to construction dust
ThermalAreas with steam or dust (shared kitchen, reprography)Less reactive than optical detector, used as complement
Linear beam detectorLarge volumes, high ceilings (atrium, loft-type floor plate)Covers long distances without multiplying points
Aspiration detectionHigh-value open space (data, shared servers in coworking)Very early detection, higher installation cost

In a conventional open floor plate, the optical detector remains the basis, supplemented by a linear detector or aspiration detection when height or equipment value justifies it.

How to calculate the number of detectors needed in an open floor plate?

The number of detectors in an open space is calculated according to the coverage area specific to each type of device, set by NBN S21-100-1, and not according to a flat rate per square metre of office. This coverage area varies with ceiling height, any roof slope, and the presence of obstacles.

High furniture (movable partitions, cabinets, suspended boxes) typical of coworking spaces create shadow zones that reduce the actual range of an optical detector, even if the nominal covered area on plan seems sufficient. A design office or installer must therefore verify the actual furniture layout, not just the empty plan, before validating the mesh. This is a point that frequently reconfigured floor plates (coworking with modular layout) must review with each significant layout change, as a mesh validated for one plan may become insufficient after rearrangement.

Who controls fire detection in an open space or coworking space?

The control and maintenance of the detection system in an open-plan office fall under NBN S21-100-2, which sets maintenance operations and periodic checks to be carried out by the operator and the approved installer. The territorially competent emergency zone (hulpverleningszone) may, as part of its opinions and controls, verify the consistency between the actual layout of the floor plate and the initially validated system.

The ANPI can be consulted for technical opinions, particularly when the open space configuration evolves significantly (partial partitioning added, floor plate extension, activity change in a coworking area). For a property manager who rents floor plates with variable layout, it is useful to have the detection mesh reassessed with each significant tenant change, rather than relying on the initial technical file.