Skip to content
SAMFire Detection Solutions
All articles

Fire detection

Multi-building fire detection: how to organize it?

  • 4 min read
  • Written and published automatically
Close-up view of a ceiling-mounted fire alarm system ensuring safety in a building.
Photo Caleb Oquendo · Pexels

Blog

In brief

On a site composed of several buildings, fire detection is organized around centralization of information to a supervision station, alarm reporting that preserves the origin of the signal, and a division into detection zones consistent with the compartmentation of each building. The architecture (one or several control panels) depends on the size of the site and must comply with standard NBN S21-100-1.

How to centralize fire detection on a site composed of several buildings?

Centralization consists of routing all detection information, alarms and faults to a single supervision point, called the central signaling station, which provides an overview of the entire site. Each building generally retains its own local fire detection control panel (CDI), which manages its own zones and triggers the alarm inside the building concerned.

This local CDI is then connected to the central station by a dedicated link (wired, bus network, or manufacturer's proprietary protocol), so that an alarm or fault signal appears immediately at the central station, with mention of the building and zone of origin. The design of this architecture falls under standard NBN S21-100-1, which sets the design and installation principles for fire detection systems in Belgium, including for installations spread across several buildings.

What is alarm reporting between several fire control panels?

Alarm reporting refers to the transmission of detection information from one control panel to another control panel or to a central station, without loss of identification of its geographical origin. On a campus, it allows an agent present in building B to know that a fire outbreak is detected in building A, and in which specific zone.

This reporting can be unidirectional (local CDIs report to a central station that only receives) or bidirectional (each control panel can also receive information from others). The choice depends on the organization of human surveillance on site: a single guard station monitoring 24 hours a day often justifies centralized reporting to this single point, in accordance with the requirements of NBN S21-100-1 on the location and operation of the alarm.

How to divide a multi-building campus into coherent detection zones?

A detection zone must correspond to a sector of the building quickly identifiable by intervention teams, generally a compartment or part of a building easily locatable from outside. On a multi-building site, each building constitutes at least one distinct zone, and is itself subdivided according to its fire-resistant compartmentation.

The classification of buildings (low, medium or high) provided by the Royal Decree of 7 July 1994 establishing basic standards for fire and explosion prevention applies building by building, according to its height and use, and determines the compartmentation requirements that then determine the division of detection zones. Consistent numbering between buildings (prefix by building, then zone number) avoids any confusion during an intervention by the emergency zone (hulpverleningszone).

Is a single control panel or several connected control panels needed for an industrial site?

The choice between a single control panel and several networked control panels depends on the size of the site, distances between buildings and daily operation. For a compact campus with close buildings, a single control panel serving all zones may suffice if cable lengths remain compatible with the technical constraints of the system.

For an extended industrial site, with distant buildings or different operators per building, several control panels connected to each other (by repeaters or network bus) offer local autonomy in case of a link failure, while maintaining the overall view at the central station. This network architecture must remain compliant with NBN S21-100-1, which frames the redundancy and reporting requirements to the monitored station or to the fire service.

What Belgian rules apply to the organization of a multi-building site?

Three texts frame the organization of fire detection on a multi-building site in Belgium. The Royal Decree of 7 July 1994 establishes the classification of each building and the resulting compartmentation requirements. NBN S21-100-1 frames the design and installation of the entire detection system, including links between control panels. NBN S21-100-2 frames the maintenance and periodic inspection of the installation.

In workplaces, the Code on Well-being at Work (Book III, Title 3) requires the employer to organize fire prevention, which includes the consistency of detection between buildings on the same site. The installed equipment must be BOSEC certified when this certification is required, and periodic inspections can be carried out by an organization accredited by ANPI or by the competent emergency zone, which also validates the organizational principle adopted.

Who coordinates detection between buildings on the same site?

Coordination between control panels and buildings on a site generally falls to the company's prevention advisor, in liaison with the certified installer who designed the overall architecture. This coordination involves a single fire safety plan for the site, harmonized numbering of zones, and regular joint tests of alarm reporting between buildings.

The maintenance register provided for by NBN S21-100-2 must cover all control panels on the site and their reporting links, with a maintenance visit at least annually. On a multi-operator site, it is useful to designate a single person responsible for the entire detection installation, even if each building remains operated separately, to prevent a local modification from breaking the consistency of alarm reporting to the central station.

Frequently asked questions

  • fire detection
  • industrial campus
  • alarm centralization
  • nbn s21-100
  • multi-building
  • detection zone

Have your system checked before someone else does it for you.

On-site audit within 48 h, no obligation. You leave with a written report, whether we work together or not.

24/7 technical standby · 0800 14 145