In brief

A chemical laboratory combines flammable vapours, exothermic reactions and extraction ducts that can propagate smoke or gas. Appropriate detection combines multi-criteria detectors (smoke, heat, CO) with specific gas detection, within the framework of the risk analysis required by the Code on Well-being at Work (Codex over het welzijn op het werk).

What are the specific fire risks in a chemical laboratory?

A laboratory or research room handling chemical products accumulates risks absent from a standard office. Flammable vapours from solvents (acetone, ethanol, ether) can form an explosive mixture with air as soon as they reach their lower explosive limit. Exothermic chemical reactions, sometimes poorly controlled during tests, release sudden heat without visible flame initially. Storage of incompatible products (oxidants and combustibles side by side) multiplies ignition scenarios. Add heating equipment in prolonged operation (ovens, water baths, hot plates) and pressurised gas cylinders. This accumulation of factors makes risk analysis specific to each room essential before choosing a detection method, rather than applying a standard solution designed for office spaces.

Why do fume hoods represent a sensitive point?

Fume hoods continuously evacuate chemical vapours out of the laboratory, but this duct network becomes a propagation vector if a fire starts or gas is released within it. A duct often crosses several fire compartments of the building: without a motorised fire damper and without detection in the duct itself, it can transport smoke or flammable vapours to rooms far from the initial incident. Automatic shutdown of ventilation in case of alarm, coupled with damper closure, limits this propagation. A detector placed at the hood outlet or in the collection network can identify an anomaly before it reaches the rest of the installation. This point deserves particular attention during design, as a poorly integrated hood remains one of the most frequent weak links in existing laboratories.

Which fire detection is suitable for a chemical laboratory?

No single detector covers all risks in a chemical laboratory: the choice depends on the nature of products handled, the ventilation in place and the room configuration. The table below positions the main detector families used in laboratories.

Detector typePrincipleRelevance in chemical laboratory
Optical smoke detectorLight scattering by smoke particlesPoorly suited alone: triggers on non-hazardous vapours or aerosols
Multi-criteria detectorCombines smoke, heat and sometimes CO, with correlation logicReduces false alarms related to solvent vapours
Gas detector (explosimeter)Measures concentration relative to lower explosive limitEssential in presence of flammable vapours
Flame detectorOptical detection of UV or IR radiationUseful for liquid fires without visible smoke

The installation design must comply with standard NBN S21-100-1, which governs the choice and installation of fire detectors.

What is a multi-criteria detector and why is it suitable for a laboratory?

A multi-criteria detector combines several measurement principles (optical smoke, temperature, sometimes carbon monoxide) in a single housing, and only triggers the alarm when the combination of signals corresponds to a real fire profile. This correlation logic avoids nuisance triggering caused by solvent vapours, steam or dust, frequent in a room where chemical manipulations occur throughout the day. In an office room, a simple optical detector generally suffices; in a laboratory, the multiplication of disturbance sources makes multi-criteria more reliable over time. However, it remains a smoke and heat detector: it does not measure the presence of flammable gases or their concentration, which requires coupling it with dedicated gas detection when explosive vapours are handled.

How to couple fire detection and gas detection in a laboratory?

Gas detection measures the concentration of flammable vapours relative to their lower explosive limit (LEL), expressed as a percentage, and triggers a technical alarm distinct from the fire alarm well before the mixture becomes explosive. This signal can be programmed to cut electrical supply to certain equipment, activate forced ventilation or, depending on the risk analysis, stop potential ignition sources. Coupling with the fire detection system is done via the control panel or a management matrix: a gas alarm can thus precede, not replace, conventional fire detection. These two functions respond to different logics: one prevents explosive atmosphere, the other detects a declared fire. The choice of risk zones and trigger thresholds falls under the laboratory-specific risk analysis, carried out with the establishment's prevention adviser.

What does the Code on Well-being at Work provide for a chemical laboratory?

The Code on Well-being at Work (Codex over het welzijn op het werk), in its Book III dedicated to workplaces, requires a risk analysis specific to each room where hazardous products are handled, including fire and explosion risk. For laboratories where explosive atmospheres may form, this analysis articulates with regulations relating to explosion risk zones (zone classification according to probability of explosive mixture presence), which conditions the choice of electrical equipment and detectors installed in these zones. The company's prevention adviser participates in this analysis and determines the technical and organisational measures to implement: ventilation, detection, extinguishing means, evacuation instructions. The Royal Decree of 7 July 1994 (Koninklijk Besluit van 7 juli 1994) establishing basic standards complements this framework for the building design itself (compartmentation, fire resistance of walls).

What maintenance to apply to a detection installation in a laboratory?

Maintenance of a fire detection installation in a laboratory follows the principles of standard NBN S21-100-2, which governs periodic inspection and maintenance of detection systems. Gas detectors require additional attention: their sensors have a limited lifespan and require regular calibration according to manufacturer specifications, failing which their trigger threshold drifts over time. Fire dampers installed in hood ducts must be tested to verify their effective closure, not only reception of the electrical signal. A BOSEC-certified installer or one referenced by ANPI can establish a maintenance plan combining these different equipment items, taking into account accelerated ageing of sensors continuously exposed to chemical vapours.

Frequently asked questions