Why does a BESS site present a particular fire risk?
A lithium-ion battery storage site (BESS, Battery Energy Storage System) presents a specific fire risk because a single faulty cell can enter thermal runaway and propagate the reaction from cell to cell, often without visible flame during the first minutes. The internal heat generated by the chemical decomposition of the electrolyte is self-sustaining, produces flammable and toxic gases, and can reach neighbouring modules by simple thermal conduction, even through an intact casing.
This mechanism makes lithium-ion battery fires different from conventional fires: they can reignite after apparent extinction (reignition), hours or even days later, as long as the residual energy stored in the cells is not dissipated. It is this particular kinetics that requires detecting the anomaly before the appearance of smoke or flame, at the stage where intervention is still possible.
What gases does a BESS release before flames appear?
Before any visible smoke, a cell in thermal drift releases gases from the decomposition of the electrolyte: hydrogen, carbon monoxide and various volatile organic compounds. This phase, called off-gassing, precedes the appearance of an open flame by several minutes.
Gas detection specifically targets this window: a sensor positioned in the envelope of the container or battery room can signal a chemical drift while the surface temperature of the module is still close to normal. This is the major advantage of this type of detection on a BESS: it precedes thermal detection and conventional smoke detection, and provides additional action time before the runaway spreads to neighbouring racks.
What early thermal detection complements gas detection?
Early thermal detection on a BESS relies on continuous temperature monitoring as close as possible to the cells, not on a point detector on the room ceiling. Three technologies complement each other depending on the site configuration.
| Technology | What it detects | Detection moment | Typical BESS use |
|---|---|---|---|
| Gas detection (hydrogen, CO, VOC) | Electrolyte decomposition before flame | Very early (off-gassing) | Inside each container or cabinet |
| Point thermal sensors on modules | Local temperature rise | Early | Cell/rack monitoring, integrated into battery management system |
| Linear thermal detection cable or optical fibre | Hot spot along a row | Early to intermediate | Rack rows, cable trays |
| Conventional smoke detection (optical, multi-sensor) | Combustion particles | Late compared to gas | Technical room, circulation area |
This combination serves the same objective: to give the alarm before the runaway becomes self-sustaining and spreads from one module to another.
Is there a Belgian standard dedicated to BESS?
There is currently no dedicated and stabilised Belgian standard specifically covering fire detection for lithium-ion battery storage sites. The applicable framework remains the general one for fire prevention in buildings.
Concretely, a BESS site remains subject to the Royal Decree of 7 July 1994 establishing basic standards for fire and explosion prevention, which classifies the building according to its height (low, medium, high) and sets compartmentation and evacuation requirements. The design of the detection system is based on the principles of NBN S21-100-1, and maintenance on NBN S21-100-2, even though these standards were not written specifically with battery chemistry in mind. For workplaces, the Code on Well-being at Work (Book III, Title 3) also requires a fire risk analysis specific to the installation. In the absence of dedicated text, it is essential to involve the competent emergency zone (hulpverleningszone) from the design phase, and to consult the technical recommendations published by ANPI on this type of emerging risk.
What measures complement detection on a BESS site?
Detection alone is never sufficient on a BESS: it must be accompanied by constructive measures and suppression systems adapted to thermal runaway. Compartmentation between racks, modules or containers limits the propagation of a faulty cell to neighbouring units, consistent with the compartment logic of the Royal Decree of 7 July 1994.
Smoke extraction from the room or container must allow evacuation of toxic and flammable gases produced from the off-gassing phase, before they reach a dangerous concentration. Separation distances between racks and between containers, as well as natural or mechanical ventilation, are among the parameters to be validated with the design office and the emergency zone. For suppression, water mist is frequently chosen for its cooling effect, the primary objective being not to extinguish a flame but to contain thermal propagation between modules. Automatic electrical isolation of the faulty module, controlled by the battery management system, completes this arrangement.
How should a Belgian installer proceed to secure a BESS?
A Belgian installer secures a BESS site by following a structured approach, in the absence of a single reference framework covering the entire subject. The following chronology reflects the steps to be followed.
- 1.Carry out a risk analysis specific to the battery chemistry installed, its energy capacity and its configuration (outdoor container, technical room, rooftop).
- 2.Contact the competent emergency zone upstream of the project, to validate the layout, fire service access and the planned compartmentation measures.
- 3.Design the detection system (gas and thermal) based on the principles of NBN S21-100-1, adapting the number and type of sensors to the rack geometry.
- 4.Select BOSEC certified equipment, compatible with the corrosive environment that gases released by batteries can create.
- 5.Commission, document the installation file and plan periodic maintenance in accordance with NBN S21-100-2.
This sequence guarantees complete traceability of the file, useful in the absence of a stabilised dedicated standard, and facilitates dialogue with the emergency zone during periodic inspections.