Why do archive rooms present a particular fire risk?
An archive repository or library concentrates a mass of paper, cardboard and bindings that constitutes a combustible load significantly higher than that of a standard office. Paper stored in dense shelving burns quickly, produces abundant smoke and sometimes smoulders in slow combustion before any visible flame, complicating late detection. An additional challenge specific to this type of building: destroyed collections (notarial archives, heritage collections, special collections) are generally not recoverable, unlike a stock of goods. This is why the preferred protection approach is not only extinguishing, but the earliest possible detection, before combustion becomes active and documents are lost.
What Belgian regulations govern fire detection in an archive repository?
The Royal Decree of 7 July 1994 establishing basic standards for fire and explosion prevention applies to these buildings and classifies them according to their height (low, medium or high-rise buildings), which determines compartmentation and evacuation requirements. The design of the detection installation then falls under standard NBN S21-100-1. For buildings occupied by workers, the Code on Well-being at Work (Book III, Title 3) requires a fire risk analysis specific to the workplace, which directly concerns staff in an archive repository or library. The territorially competent emergency zone (hulpverleningszone) provides an opinion on the project and carries out inspections.
Which detection technology should be chosen for a high combustible load?
The choice depends on the combustion stage to be detected: an optical smoke detector reacts to visible particles, a linear detector suits large open volumes, and aspirating smoke detection (ASD) detects sub-visible particles from the slow combustion phase of paper, even before perceptible smoke appears.
| Technology | Principle | Relevance for archives |
|---|---|---|
| Point optical detector | Reacts to light scattering by visible smoke | Late detection in large volumes |
| Linear detector (beam) | Monitors an axis between transmitter and receiver | Suitable for large volumes but less sensitive to smouldering phase |
| Aspirating smoke detection (ASD) | Continuously samples air via a network of pipes and analyses it by laser | High sensitivity, detection from paper carbonisation stage |
What is aspirating smoke detection and why is it suitable for archives?
Aspirating smoke detection (ASD) is based on a network of perforated pipes installed in ceilings, shelving or raised floors, connected to a control unit that continuously aspirates small volumes of air for analysis by a highly sensitive laser sensor. This principle allows detection of combustion particles well before a conventional point detector would react, which is crucial for paper that smoulders slowly before igniting. ASD is particularly suitable for compact shelving and high storage heights, where air dilutes quickly and delays smoke reaching a point detector, as well as for air-conditioned rooms where air circulation reduces locally perceived smoke concentration. It integrates into an installation designed according to NBN S21-100-1, in the same way as conventional detectors.
How should maintenance of a detection installation in an archive repository be organised?
Maintenance and periodic inspection of a fire detection installation, whether conventional or aspirating, are governed by NBN S21-100-2. For an ASD system, this maintenance includes verification of aspiration flow in each pipe, checking or replacing filters, and testing laser sensor sensitivity—specific operations that supplement the usual checks of a detection control panel. Using equipment certified BOSEC and an installer recognised by ANPI ensures that equipment and its implementation meet Belgian regulatory requirements. In an archive repository, sometimes restricted access to shelving (mobile carriages, storage height) must be anticipated in the maintenance contract, so that maintenance operations remain feasible without heavy dismantling of storage installations.
Should early detection be coupled with an automatic extinguishing system?
Coupling early detection with automatic extinguishing makes sense in an archive repository, provided an agent is chosen that does not destroy documents at the very moment it protects them. Sprayed water (sprinkler) irreparably damages paper, which often leads to preferring gaseous agents or very low-flow water mists for areas with high heritage value. Aspirating smoke detection, thanks to its speed, allows triggering an alarm or even automatic extinguishing at a stage where smoke volume and heat remain limited, reducing the extent of collateral damage. This choice of extinguishing agent must be defined with the installer and validated in the risk analysis, consistent with the compartmentation required by the Royal Decree of 7 July 1994 for the building category concerned.