What is the specific fire risk in a sorting or recycling centre?
A sorting or recycling centre combines heterogeneous combustible materials (paper, wood, plastics, textiles, organic waste) stored in large volumes, often outdoors or under canopies, with mechanical processes generating dust and heat (shredding, compacting, conveying). This combination creates a risk rarely found in conventional tertiary buildings: self-heating of materials, which can lead to spontaneous ignition without any external ignition source.
Belgium does not have consolidated official statistics on fires by sector of activity: UGent notes this lack of systematic data. We only know that approximately 10,000 fires occur each year in buildings in Belgium, across all sectors. For a sorting site operator, the practical observation remains identical to that of any company affected by a major incident: 70% of these companies never recover, according to the European Fire Sprinkler Network.
Why does self-heating complicate fire detection?
Self-heating refers to a slow temperature rise in a pile of materials, caused by an internal biological or chemical oxidation reaction, without visible flame for hours, sometimes days. The fire smoulders at the heart of the stock before emerging at the surface.
This development mode makes conventional point smoke detectors poorly suited on two levels. Firstly, a pile of waste outdoors or under an open shelter dilutes the smoke before it reaches a point detector placed at height. Secondly, the dusty atmosphere generated by shredding and conveying saturates conventional optical detectors with false alarms, which often leads operators to deactivate them, which is worse than the absence of detection. The risk is therefore not only thermal, it is also a risk of failure of the monitoring system itself if the technology is not suited to the environment.
Which detection technologies are suitable for these dusty environments?
No single technology covers an entire sorting centre. The combination of several detection principles, adapted to each zone (outdoor storage, sorting hall, process line), is the only approach consistent with an evolving risk and a dust-laden atmosphere.
| Technology | Principle | Suited to |
|---|---|---|
| Aspirating smoke detection (ASD) with filtration | Continuously aspirates air, filters coarse particles, analyses fine smoke | Sorting halls, confined zones, technical rooms |
| Thermal camera | Maps the surface temperature of piles, detects hot spots before flame | Outdoor stocks, screening zones, shredding areas |
| Linear heat-sensing cable | Triggers on temperature threshold or gradient along its route | Conveyors, tunnels, extended linear zones |
| Infrared/ultraviolet flame detector | Detects the radiation of an open flame | Zones at risk of rapid ignition (liquids, residual solvents) |
The thermal camera has a specific advantage on this type of site: it allows continuous monitoring of the temperature of material piles, useful for detecting self-heating before any visible smoke emission.
How to combine these technologies on a site where stocks are constantly moving?
A sorting centre does not have a fixed configuration: material piles move, grow, empty at the rhythm of truck rotations. Detection must therefore be designed in functional zones rather than rigid fixed points, with mobile or broadly covering technologies rather than isolated point detectors.
Concretely, this means combining aspiration detection in closed and confined volumes, thermal cameras monitoring outdoor or canopy storage areas, and heat-sensing cables along conveyors and tunnels where point detection would be ineffective. This multi-criteria approach, where several technologies cover the same zone with different physical principles, reduces both the risk of non-detection of a smouldering fire and the risk of false alarm linked solely to the presence of dust. The precise choice depends on the site configuration, the nature of the sorted materials and the organisation of flows, which justifies a specific risk study before any dimensioning.
What does Belgian regulation provide for detection on these sites?
The design of a fire detection installation in Belgium, including on an industrial sorting or recycling site, must comply with standard NBN S 21-100-1, which sets the design and installation rules for fire detection systems. The Code on Well-being at Work (Book III, Title 3) (Codex over het welzijn op het werk) also governs fire prevention in workplaces, which directly concerns personnel exposed on this type of site.
The Royal Decree of 7 July 1994 (Koninklijk Besluit van 7 juli 1994) establishing basic standards for fire and explosion prevention applies to buildings according to their classification (low, medium, high), a criterion to be verified case by case for ancillary constructions of a sorting site. The territorially competent emergency zone (hulpverleningszone) remains the contact point for opinions and inspections on this type of installation, particularly when the site includes specific risks such as tanks, ATEX zones or high-level storage.
What maintenance must be planned for these specific installations?
The maintenance and inspection of a fire detection installation are governed by standard NBN S 21-100-2, which requires periodic inspection by a competent service. On a dusty site such as a sorting centre, this normative periodicity must be accompanied by increased vigilance on the fouling of detectors and aspiration filters, which clog faster than in a tertiary environment.
The use of BOSEC-certified equipment guarantees that the installed equipment meets the performance requirements recognised in Belgium. ANPI can also support the operator in risk assessment and the choice of equipment suited to the site atmosphere. More frequent cleaning and verification of thermal cameras and aspiration heads, beyond the strict normative minimum, are often necessary to maintain detection reliability under these particular operating conditions.