Which fire detection to protect archives and museum collections?

  • 4 min read
  • Written and published automatically
Silhouetted chimneys emit smoke into the sky creating an industrial scene.
Photo Francesco Ungaro · Pexels

Blog

In brief

For archives, libraries and museums, fire detection must be very early: aspiration systems and high-sensitivity smoke detectors enable intervention before any visible flame, as smoke alone already destroys irreplaceable assets. In a heritage building, this detection must also integrate without disfiguring the listed décor.

Why is very early detection essential for heritage collections?

Very early detection is preferred for archives, libraries and museums because damage begins before a flame appears. Archive paper, parchment or canvas exposed to smoke, soot or a simple temperature rise already suffers irreversible degradation, well before conventional detectors react. Unlike an office or warehouse, these assets cannot be replaced: documentary or heritage loss is permanent, whereas an industrial building can be rebuilt. The objective is therefore no longer simply to evacuate people and limit spread, but to detect the phenomenon from the slow combustion phase (pyrolysis), even before any visible flame. It is this gap of a few minutes, gained by very high sensitivity detection, that makes the difference between a contained incident and a lost collection. This is why conservation rooms, reserves and archive repositories justify solutions far exceeding the requirements of a standard tertiary space.

Which detection technologies suit archives, libraries and museums?

Several detection technologies coexist depending on the required sensitivity and room configuration. The choice depends on the volume to be monitored, ceiling height and the speed of reaction required for an irreplaceable collection.

TechnologyPrincipleSensitivityTypical use in heritage environment
Point optical detectionLight scattering by smoke particlesStandardOffices, circulation areas, standard exhibition rooms
Aspiration detection (ASD)Continuous air sampling analysed in central unitVery high, early detectionArchive reserves, museum repositories, conservation rooms
Linear smoke detectionOptical beam over long distanceStandard to highLarge volumes, exhibition halls, high attics
Flame detectionInfrared or ultraviolet sensorsFast on open flameSpecific risk areas (restoration workshops)

The design of these installations falls under standard NBN S 21-100-1, which governs the choice and installation of detectors according to the type of protected space.

How does aspiration detection work in a conservation room?

Aspiration detection (ASD, Aspirating Smoke Detection) works by continuous sampling of ambient air via a network of perforated tubes, the air then being permanently analysed by a very high sensitivity optical central unit. This principle enables detection of smoke concentrations well below the threshold perceptible by a conventional point detector, therefore from the first moments of slow combustion onset.

This technology presents a dual benefit for archives and museums. On one hand, it offers the shortest reaction time available on the market, which is decisive for assets that smoke degrades before flame. On the other hand, aspiration tubes are discreet, installed in false ceilings or along structures, without multiplying visible boxes in an exhibition room or a controlled-atmosphere reserve. However, the tube network layout must be carefully studied in temperature and humidity-controlled spaces, to avoid disturbing conservation air flows.

How to integrate fire detection without disfiguring a heritage building?

Aesthetic integration of fire detection in a listed building consists of reconciling collection protection with preservation of décor, woodwork, painted ceilings or protected façades. In this context, any groove in ancient masonry or any visible fixing on a listed element may be excluded outright by the heritage manager or competent authority.

The preferred technical solutions are generally: routing cables and aspiration tubes through existing voids (attics, ducts, false ceilings), choosing small-diameter detectors or colour-matched to the support, and using remote sampling points rather than visible boxes in public rooms. Aspiration detection lends itself well to this exercise, since only a small sampling orifice remains visible, the processing unit being installed in a remote technical room. Each project in a heritage building is therefore built in consultation between the installer, curator and, where applicable, the body responsible for protecting the asset.

Which Belgian regulatory framework applies to museums and archive centres?

Museums, libraries and archive centres accessible to the public fall, like any building, under the basic standards set by the Royal Decree of 7 July 1994 on fire and explosion prevention, which classifies buildings according to their height (low, medium, high) to determine compartmentation and equipment requirements. When these places employ staff (curators, security officers, maintenance personnel), the Code on Well-being at Work (Book III, Title 3) additionally imposes fire prevention measures in workplaces.

Detection system design follows standard NBN S 21-100-1, and installed equipment must bear BOSEC certification when required. The territorially competent emergency zone (hulpverleningszone) issues the opinion on the project and performs inspections, while ANPI may be consulted as a technical reference body. For a listed heritage collection, these requirements are superimposed on, without replacing, obligations specific to built heritage protection.

What maintenance for a detection system in a museum environment?

Maintenance of a fire detection system in a museum or archive environment follows operations defined by standard NBN S 21-100-2, which governs the maintenance and periodic inspection of fire detection installations in Belgium. This standard sets the nature of checks to be performed (detector operation, aspiration network condition, central unit tests) without limiting to simple visual inspection.

For aspiration detectors, a specific attention point concerns air flow in tubes, which may vary with fouling or room modification (new furniture, reserve partitioning). In humidity-controlled spaces, maintenance operations must be planned to avoid disturbing conservation conditions, for example by limiting door openings during tests. The building manager benefits from maintaining precise traceability of these interventions, which serves both in case of emergency zone inspection and in case of incident, to demonstrate that the installation was maintained in accordance with the standard.

Frequently asked questions

  • fire detection
  • heritage
  • museum
  • archives
  • aspiration detection
  • listed building